A window air conditioner produces 5 to 20 pints of condensate on a humid day, and every ounce of it is supposed to drain out the back. When you find a window unit leaking water inside, the cause is almost always one of three things: the unit is pitched the wrong way, the rear drain is blocked, or the evaporator coil has frozen and is now thawing. Each fix takes less than an hour and rarely costs more than $10 in parts.
Part of our Windows & Doors guide — explore the full guide →
Before you tear the unit out of the window, check the level. A cheap mistake during installation accounts for most leaks on units less than two years old.
Check the Tilt First
A window AC must sit with the back about a quarter inch lower than the front, roughly half a bubble off level on a standard 24-inch torpedo level. That slope sends condensate toward the rear drain port. If the front sits too low, water pools in the indoor pan and overflows onto your floor.
Set a 24-inch level on top of the cabinet. If the bubble centers or leans toward the back of the room, the unit is pitched wrong. Loosen the mounting brackets, lift the front edge, and shim under the indoor lip with a strip of cedar shake or a Frost King window AC support bracket ($24 at Lowe’s). Manufacturers like LG, Frigidaire, and GE all specify the same backward pitch in their install manuals, so this fix applies across brands.
Clear the Rear Drain Port
The exterior side of every modern unit has a small drain hole or slinger ring designed to fling water onto the condenser coil for evaporative cooling. Pollen, leaves, and insect nests block this hole within a single cooling season. Pull the unit halfway out of the window (have a helper hold it) and inspect the bottom pan from below.
Push a 12-gauge copper wire or a pipe cleaner through any clogs. A bent paperclip works on smaller units like the GE AHQ06LZ. Some Friedrich and LG models include a side condensate kit with a 3/8-inch barbed fitting where you can attach a vinyl hose and route water to a drip pan, which is the cleanest solution if you have the option.
Diagnose a Frozen Evaporator Coil
Switch the AC off and remove the front grille. If the indoor coil is encased in ice or beaded with frost, you have a freeze-up. Frozen coils thaw into the indoor pan faster than the drain can handle, which produces a sudden flood about 30 minutes after shutdown. The three usual causes:
- Dirty filter: Insufficient airflow drops coil temperature below 32°F. Wash the filter monthly in warm soapy water.
- Low refrigerant: R-410A units that have lost charge run at abnormally low pressures and freeze. This is a sealed-system repair and requires an EPA Section 608 certified technician.
- Running below 60°F outdoors: Most units are not designed for outdoor temps under 60°F. Use them only in summer.
Inspect the Condensate Pan
Pull the chassis from the cabinet (unplug first) and look at the indoor drain pan. Algae buildup, hair, and dust create a sludge that blocks the small weep slot leading to the rear pan. Wipe the pan with a mixture of one cup distilled white vinegar to one gallon water. For heavy biofilm, drop in a Pan Tablet (Nu-Calgon 4296-50, about $9 for a 12-pack), which dissolves slowly over a few weeks and keeps slime from reforming.
Check the divider wall between front and rear pans for cracks. A hairline crack lets indoor condensate seep onto the windowsill. JB Weld PlasticWeld ($6) repairs ABS divider walls permanently if you clean the surface first with isopropyl alcohol.
Verify the Window Seal
Rainwater entering the room can masquerade as a leaking AC. Look at the side curtains, the foam strip between the upper and lower sash, and the caulk line above the unit. Pittsburgh-style sash gaskets compress over time and let wind-driven rain past. Frost King AC42H foam tape ($5 a roll) seals the upper sash gap. Run a bead of GE Silicone II clear sealant ($8) along the exterior top of the unit if water tracks down the window above.
This step matters most during summer thunderstorms when leaks appear suddenly and only during rain.
Brand-Specific Quirks
LG units made between 2016 and 2020, particularly the LW8016ER, are known for a too-shallow rear drain that overflows in humid coastal climates. The factory remedy is a service bulletin recommending an aftermarket drain spout kit, available from PartSelect for around $18. Frigidaire FFRE0833U1 owners report similar issues fixed by drilling a 1/4-inch overflow hole in the rear corner of the pan, but this voids the warranty so check coverage first.
GE Profile and Haier inverter models include a built-in evaporative pump. If the pump fails, water backs up. Replacement pumps run $35 to $60 and are user-serviceable on most models if you can read a wiring diagram.
When to Replace Rather Than Repair
A 10,000 BTU unit costs $260 to $400 new, while a service call from an HVAC tech runs $90 to $150 per hour plus parts. If your unit is over eight years old, leaks repeatedly, or runs at an EER below 10, replacement makes more sense than repair. Look for ENERGY STAR certified models like the Midea U MAW08V1QWT, which uses a U-shaped design to seal the window with the sash closed and effectively eliminates the rain-infiltration issue.
Preventing Future Leaks
Pull the unit out every fall, hose the coils, and store the chassis indoors. Reinstall in spring with a fresh foam gasket, fresh side curtains, and a level check. Once a month during cooling season, pull the filter, rinse it under hot water, and verify that water is dripping from the back of the unit. A few minutes of inspection saves you from finding a window unit leaking water inside onto a hardwood floor at 2 a.m.